ECC-FFT Instruction Manual — P/N LS10031-000FL-E:B 9/4/2013

15

ECC-FFT Fire Fighter Telephone Module Connection

Installation

2.5 ECC-FFT Fire Fighter Telephone Module Connection

The ECC-FFT provides connection for a single Class B or Class A telephone audio circuit. See
page 21 through page 26 for examples of audio zone configurations. An MMF-301 monitor module
can be used to monitor the connection of the Fire Fighter Telephone remote handset (FHS-F) into
the FPJ-F, which is then displayed on the ECC-FFT active zone LED during the Autoprogram fea-
ture.

0

10

11

12

13

14 15

ADDRESS

LOOP

1

2

3

4

TENS

ONES

6

7

8

9

5

0 1

2

3

4

6

7

8

9

5

TB1

TB2

3
2
1

1
2
3

+

-

+

-

To FFT - SLC Terminal TB4

Connectors or other MMF-301

The wiring between the monitor

module and FPJ-F is supervised

by the monitor module. A 47K

End-of-Line resistor is built into

the FPJ-F.

To FFT-Phone TB4 phone

In/Out + – connections or other

FPJ-Fs

4.7K

, 1/2 watt ELR

(install on last device for Style Y

[Class B] telephone circuit only

FFT-FPJ

Figure 2.5 ECC-FFT Connections