Caution – HT instruments PQA824 User Manual

Page 50

Advertising
background image

PQA400 - PQA823 - PQA824

EN - 49

The opposite situation is the error due to a too many selected parameters. In this case the
below screen is shown:

12/09/2006 – 16:55:10

RECORDING SETTINGS

+ General Parameters

+

Harmonics

Voltage Anom.: 230V 6%-10%

Inrush current: 30A 1s fix

Flicker

Unbalance

Error: too many selected parameters 440/251

CLP/EXP

PREDEF.

SEL

MODIFY

Fig. 94: General Parameters section: too many selected parameters

In the above screen (see Fig. 94) the harmonics' selection brought about too many
selected parameters (more than 251). Not select some parameters to quit this situation.

CAUTION

The choose of a electrical for recording often increase the number of
selected parameters more than one unit only. In particular:

Frequency

 1 selected parameter.

Voltage

 from 1 to 7 selected parameter depend on system.

Current

 from 1 to 4 selected parameter depend on system.

Powers and Energies

 from 1 to 8 selected parameter depend on

system and Cogenerations.

Power Factor

 from 1 to 8 selected parameter depend on system and

Cogeneration.

Harmonics: THD and DC

 from 1 to 8 selected parameter depend on

system.

Harmonics Odd

 from 25 to 100 selected parameter depend on

system.

Harmonics Even

 from 24 to 96 selected parameter depend on

system.

Voltage Anomalies

 no selected parameters.

Flicker

 from 1 to 3 selected parameter depend on system.

Unbalance

 1 selected parameter.