4.1.5 Output configuration

Figure 19 ProfiSoft Output Configuration.

Output Configuration

:

Output Values: The setting for the lower/higher alarm and warning limits.
Alarm Hysteresis: Hysteresis expressed in the engineering units of the output value scale.

An alarm occurs when a value exceeds an upper limit. The alarm's status remains true until

the value drops below the limit minus the alarm hysteresis. The directions are reversed for
low limit detection. The hysteresis is also used for the warnings.

Unit: Engineering unit for the output value.
Measure type: If sensor connections are Resistance 2 x 3 Wire or Voltage 2 x T/C, select the

type of measuring results (output). The selected Measure type will be valid on FB1

(Function Block 1) while Input channel 1 will be valid on FB2 and Input channel 2 on FB3.
Display Output: Turns the communication port of the transmitter into an output to an LCD-

display and sets number of decimals to be shown on the display. Also sets the number of

decimals shown in the View Signal window in ProfiSoft.
Filter Time: This parameter contains the time constant for the rise time of the output up to

a value of 63,21% resulting from a step at the filter input. The engineering unit of this
parameter is always second.

Sensor Wire Monitoring: Enables the lead breakage and short circuit detection.

Sensor Low Isolation Monitoring: A monitoring of the internal isolation level in RTDs and
T/Cs. If the isolation falls below the set “Isolation limit”, a message will be transmitted.

Sensor Aging: Compare if the input value for channel 1 differs the input value for channel 2.
If the difference is larger than the entered limit a status signal is set and can be read by the

PLC system. The limit has the same unit as the input signal.