INOR PROFIPAQ-L User Manual

Page 29

Advertising
background image

29

5.3 PROFIBUS/ProfIPAQ parameters

ProfIPAQ have the possibility to send 3 function blocks (if they are selected in the PLC

program) to the PLC (cyclic communication). The function blocks contain 5 bytes, the first 4
bytes are the value, and the last byte is the status.



Value (4 bytes)

Status (1 byte)

FB1

Output Value

Se table FB1 Status

FB2

Input Value Channel 1

Se table FB2 Status

FB3

Input Value Channel 2

Se table FB3 Status

Table 1 ProfIPAQ parameters


Status (Hex)

Description

0x80 God
0x84

Active Block Alarm

0x89

Active Advisory Alarm. Below Lower Limit Alarm (Lower

Warning)

0x8A

Active Advisory Alarm. Over Upper Limit Alarm (Upper

Warning)

0x8D

Active critical alarm. Below Lower Limit Value (Lower Alarm)

0x8E

Active critical alarm. Over Upper Limit Value (Upper Alarm)

Table 2 FB1 Status



Status (Hex)

Description

0x00 God
0x01 Underrange
0x02 Overrange
0x04 Lead

Breakage

0x08 Short

Circuit

0x40 Sensor

Isolation

0x80 Sensor

Aging

Table 3 FB 2 Status


Status (Hex)

Description

0x00 God
0x01 Underrange
0x02 Overrange
0x04 Lead

Breakage

0x08 Short

Circuit

Table 4 FB 3 Status

Advertising