1 changing the default power-up settings, 3 power supply basics, 1 controls and indicators – KEPCO BOP-GL 1KW Operator Manual Firmware Ver.3.05 and higher User Manual

Page 64: Changing the default power-up settings -2, Power supply basics -2, Controls and indicators -2, R. 3.3 for, R. 3.3 power

Advertising
background image

3-2

BOP-1K-GL 022814

Voltage mode (Current mode)

internal control, ± limit values at max (1.01 x E

Onom

or I

Onom

)

(internal control, +limit values at maximum (1.01 x E

Onom

or I

Onom

),

–limit values at minimum (box))
(internal control, –limit values at maximum (1.01 x E

Onom

or I

Onom

),

+limit values at minimum (box))
(External protection limits)

GPIB address 6 (0 to 30)

All the above settings can be changed either by using the top cover-accessible switches while
power is off, or by sending SCPI commands if using digital control.

3.2.1

CHANGING THE DEFAULT POWER-UP SETTINGS

The default power-up settings listed in PAR. 3.2 can be changed as follows:

1. To change Load type, Trigger port pin 2 remote on-off logic or RS 232 baud rate, refer to

PAR. 3.3.2.1 for Reset Power-up.

2. To change all other power-up switch settings refer to PAR. 3.3.2.2 for normal power-up.

NOTE: All power-up settings can be changed by digital command, and if desired, the digitally

changed setting can be saved for power-up using the MEM:UPD command (see PAR.
B.12). However it is recommended that the unit be tagged with all settings saved for
power-up to avoid unexpected behavior upon power-up.

3.3

POWER SUPPLY BASICS

The following paragraphs describe basic operation of the front panel controls and indicators
(PAR. 3.3.1), how to turn the unit on, including how to change the power-up defaults (PAR.
3.3.2), and an explanation of the basic techniques and principles needed to operate the power
supply.

When in Voltage mode, the power supply will (within the configured and rated limits) provide the
programmed output voltage. Current is determined by the load, and cannot exceed the Current
Protect limits. If the protect limit is reached, the POWER/FAULT/LIMIT LED light changes from
green (power OK) to orange.

When in Current mode, the power supply will (within the configured and rated limits) provide the
programmed output current. Voltage is determined by the load, and cannot exceed the Voltage
Protect limits. If the protect limit is reached, the POWER/FAULT/LIMIT LED light changes from
green (power OK) to orange.

3.3.1

CONTROLS AND INDICATORS

Refer to Table 3-1 and Figure 3-1 for a description of front panel controls and indicators.

Advertising