KROHNE BM 100A Handbook User Manual

Page 19

Advertising
background image


Handbook BM 100 A

19


2.2.2 Wiring

connections


Open the signal converter housing rear cover, using the plastic wrench supplied. The terminal
connections are labelled. The standard connections are shown below.


Before starting to wire:

• check that the power supply corresponds to the power board installed.

• check which output option you have selected: this will be indicated on the underside of the rear

housing cover and on the gauge nameplate.


Terminal layout : non – Ex version

X = Terminal not used (X) = Terminal not used except for RS485 outputs

Ensuring a good contact and protection of wire strands

Local regulations concerning electrical wiring must be followed and obeyed. If no details are
given, we recommend :
• crimped metal sheaths over the wire strands

• power supply cables should be rated for at least 500 V, with a cable diameter of 0.5 to 1.5

mm / 0.02” to 0.06” (non-Ex applications only).

• the output current cable diameter should be from 0.5 to 0.75 mm / 0.02” to 0.03”



PE Ground Terminal notes

The internal earth connection shall be used according local applicable installation standards, in
Europe the Low voltage Standard prescribes the connection of the yellow/green cable in case of
230VAC.