Handbook BM 100 A


Function (Fct.)

Input Range

Description

1.2.0 DISPLAY

To display readings in the form and
units required.

Select SINGLE or
CYCLIC display mode.

1.2.1 DISP.

MODE

(Display Mode)

SINGLE

Cyclic mode permits more than one
item to be displayed in a cycle when
used with Functions 1.2.2 and 1.2.3.

Select parameter(s) to be
displayed. Parameters:
Level, Distance, volume
interface level, layer,
interface distance,
interface volume, ullage
volume and percentage
of output 1 (if in single
mode).

1.2.2 DISPL.

ITEM

(Display Item)

Level

Single Display Mode: One parameter
is displayed in the operating mode.
Cyclic Display Mode: One or more
parameters are displayed in the
Operating Mode. Simply select this
function, select a parameter and press
“Right” to confirm.
Repeat this procedure to add
parameters to be displayed.

Enter 1 to 10 seconds

1.2.3 CYCLIC

TIME

1 second

Sets the amount of time a reading is
displayed in cyclic operating mode.

Select (0.01) m, (1) cm,
(1) mm, 0.1 mm, (0.1)
inch and (0.01) feet

1.2.4 LGTH

UNIT

(Length Unit)

mm

Sets the length units for displayed
readings.

Select (0.01) cubic
metres, (0.1) liter, (0.1)
US gallon, (0.1) GB
gallon, (0.1) cubic feet,
(0.1) barrel, (1) kg, (0.01)
metric ton, (0.01) GB ton
or (0.01) US ton.

1.2.5 VOL.UNIT

(Volume Unit)

m3

Sets the volume units for displayed
readings.

Select YES or NO

1.2.6 ERROR

MSG

(Error Message)

NO

Turns an error indicator on or off. If
configured “YES”, the display flashes
when a reading error occurs.