5

3 Preparation for measurement

Before testing, always check the following:-
1.The“low battery”Indication“

”is not displayed

2.There is no visually obvious damage to the tester or to the test leads
3.Test the continuity of the test leads by switching to continuity test and

shorting out the lead ends. A high reading will indicate that there is a faulty
lead or that the fuse is blown.

4.

MAKE SURE THAT THE CIRCUIT TO BE TESTED IS NOT LIVE. A

warning lamp is lit if the instrument is connected to a live circuit but test the
circuit as well!

5

4 Insulation resistance measurement

Model 6011A has a selectable, triple test voltage of 250V, 500V and 1000V DC.

1.Select the insulation resistance setting by rotating the function dial to the

required test voltage - 250V, 500V or 1000V as indicated under the

“insulation”test section of the functional switch, after making sure that the

instrument is not connected to a live circuit.

2.Attach the test leads to the instrument and to the circuit or the appliance

under test (see Figs 7 & 8)