KYORITSU 6011A User Manual

Page 9

Advertising
background image

― 7 ―

Function

Rated

Voltage

Measuring Range

Accuracy

Voltage Measurement-

100-250V

100-250V

3% rdg

To prevent wrong connection of test leads and to maintain safety, the dedicated
terminals used for continuity and insulation tests are automatically covered
when using the terminals for loop impedance, PSC and RCD tests

● Typical Number of Tests (central tendency for supply voltage up to 8V at R6)

Insulation Resistance Ranges : Approx. 500 times min. at load 0.5MΩ
Continuity Ranges

: Approx. 300 times min. at load 1Ω

LOOP.PSC.RCD Ranges

: Operational lifetime:5h (In case of

continuous duty)

Operating error

● Operating Errors (IEC 61557-2,-4)

Function

Range

250V
500V

1000V

0.25~199.9MΩ
0.50~199.9MΩ
1.00~199.9MΩ
0.20 ~ 19.99Ω
10.0 ~ 199.9Ω
100 ~ 1999Ω

20Ω
200Ω
2000Ω

Measuring range to keep
operating error

Maximum percentage
operating error

±30%

Insulation

Continuity

Function

RCD X 1/2

Accuracy

Rated Voltage

(AC)

Trip Current

Trip Current

Duration

230V+10%-15%

50Hz

230V+10%-15%

50Hz

230V+10%-15%

50Hz

RCD X 1

RCD X 5

10/30/100/300/

500/1000 mA

10/30/100/300/

500/1000 mA

30/100/300mA

(Note:on × 5

range maximum

current that can

be generated is

1A)

2000ms

2000ms

1000mA@200ms

50ms

Trip Current:

-10% +0% of

range at 230V
Trip Current:

+10% -0% of

range at 230V
Trip Current:

± 10% of

range at 230V

10 mA

Trip Current:

+10% -0% of

range at 230V

Trip Time
±(1% rdg
+ 3dgt)