KYORITSU 6011A User Manual

Page 22

Advertising
background image

― 20 ―

Fig 9

6.5 Loop impedance at 3 phase equipment
In order to test the Loop impedance at 3 phase equipment the optional OMA
DIEC(Model7133) is necessary.
Use the same procedure as in 6.4 above ensuring that only one phase is
connected at a time i.e.:First Test: red prod to phase 1, black prod to neutral,

green crocodile clip to earth.

Second Test: red prod to phase 2, black prod to
neutral, green crocodile clip to earth etc.

WARNING

N EVE R CON N ECT TH E I NSTR U M E NT TO TWO

PHASES AT THE SAME TIME.

Testing as described in 6.4 and 6.5 above will measure the Phase-Earth loop
impedance. If you wish to measure the Phase-Neutral loop impedance then the
same procedure should be followed except the earth clip should be connected
to the neutral of the system i.e.: the same point as the black neutral probe.
If the system has no neutral then you must connect the black neutral probe to
the earth i.e.: the same point as the green earth clip. This will only work if there
is no RCD in this type of system.