Measurement method
Swell/ Dip/ Int/ Inrush current

Each event will be detected with the r.m.s. values in one gapless waveform and with a half-wave over-
lapping. The beginning of the waveform where the first event is detected is regarded as the start of the
event. If further events are not detected in the following waveform, the beginning of the waveform is
regarded as the end of the event. The detected event is assumed to be continued between the start to
the end of event detection.

Example: Dip event detection

*

Int events are detected in the same method.



Example: Swell event detection

*

Inrush current events are detected in the same method.

rms value(1)

rms value(2)

rms value(3) rms value (5) rms value (7) rms value(9)

rms value(4) rms value(6) rms value(8)

Measured
waveform

rms value(1)

rms value(2)

rms value(3) rms value(5) rms value(7) rms value(9)

rms value(4) rms value(6) rms value(8)

Measured
waveform

RMS waveform

Start of dip

End of dip

duration

Hysteresis

Threshold

(4)

(5)

(6)

(7)

(8)

(9)

(1)

(2)

(3)

RMS waveform

Start of swell

duration

End of swell

(4)

(5)

(6)

(7)

(8)

(9)

(1)

(2)

(3)

Threshold