Measurement setting

Setting item

Details of setting

Demand

Interval

Not be used/ 10min/15min/30min

Inspection

cycle

Interval: 10min/ 15min

1min/2min/5min

Interval: 30min

1min/2min/5min/10min/15min

Target

0.001mW-999.9TW(100.0kW)

Harmonics

THD(total harmonic distortion) calc.

THD-F(based on the fundamental waveform)/

THD-R(based on all rms values)

Allowable range

Default/ customize(V/A)

MAX HOLD

ON/OFF

Power quality

Hysteresis

against nominal V: 1 to 10%(5%)

Transient

against nominal V: ±50 to ±2200Vpeak(300%)

Swell

against nominal V: 100 to 200%(110%)

Dip

against nominal V: 0 to 100%(90%)

Int

against nominal V: 0 to 100%(10%)

InrushCurrent

against “A” range: 0 to 110%(100%)

Flicker

Filter (Ramp)

230V/220V/120V/100V

Capacitance

calculation

Target PF

0.5-1(1.000)

Recording setting

Setting item

Details of setting

Recording

item

Harmonics

Record/ Do not record

Power quality (event)

Record/ Do not record

Recording

method

Interval

1sec/2sec/5sec/10sec/15sec/20sec/30sec/

1min/2min/5min/10min/15min/20min/30min/

1hour/2hours/150,180 cycles (approx 3sec)

Start

Manual/Constant rec./Time period rec.

Constant

measurement

REC Start

Day/ Month/ Year Hour: Minute (00/00/0000 00:00)

REC End

Day/ Month/ Year Hour: Minute (00/00/0000 00:00)

Timer

Rec. period

Start-End

Day/ Month/ Year (DD/MM/YYYY)- Day/ Month/ Year (DD/MM/YYYY)

Time period

Start-End

Hour: Minute (hh:mm)- Hour: Minute (hh:mm)

* Default values are highlighted in gray.

Save setting

Setting item

Details of setting

REC data

Delete data.

Transfer data.

Format

KEW6315 setting

Save setting.

Read settings.