LEVEL A

Function

Options

[Factory settings] shown in brackets

Linear Input Scaling

Please read in conjunction with Linear Input Set-up Procedure on page 6.

An.hi

-1999 to 9999

[1000]

Adjusts required scale maximum

An.Lo

-1999 to 9999

[0]

Adjusts required scale minimum

hi.in

0.1 to 50.0

[50.0]

Configure input maximum

Lo.in

0.0 to 49.9

[10.0]

Configure Input minimum
This setting must be at least 0.1 less than the setting for

hi.in

above.

Note: Refer to Linear Input conversion factors detailed in the Set-up Procedure on page 6.

dECP

000.0 to 00.00

[0000]

Scale resolution
NB. Once the Linear Input option has been selected, the setting here over-rides the scale
resolution setting

di.SP

in Level 2 and will affect the following display readings:

Level A:

An.hi

;

An.Lo

;

Set.3

;

hYS.3

Level 1:

bAnd

;

ofSt

;

SPrr

;

SEt2

;

bnd.2

Level 2:

hiSC

;

LoSC

Level 3:

SPAn

;

ZEro

;

rEAd

;

tECh

SP3 SETTINGS

SP3.A [nonE]

dV.hi dV.lo bAnd FS.hi FS.Lo EoP

Main SP3 operating mode

SP3.b [nonE]

LtCh hoLd Lt.ho

Subsidiary SP3 operating mode

SEt.3

0 to 2500

[0]

SP3 setpoint adjustment

hyS.3

0.1 to 100% of hiSC

[20]

Set SP3 hysteresis

10

LEVL A

Function

Options

[Factory settings] shown in brackets

brn.3 [uPSC]

uPSC or dnSC

Sensor burn-out / break protection
Select upscale or downscale

rEV.3 [3d]

3d or 3r

Reverse SP3 output mode
Select direct or reverse operation

Will be affected by

dECP

settings in Level A