9

Function

Options

[Factory settings] shown in brackets

rEu.d

Select output modes: Direct/Reverse

Caution: Settings affect fail safe state.

SP1

SP2

[1r.2d]

Reverse

Direct

1d.2d

Direct

Direct

1r.2r

Reverse

Reverse

1d.2r

Direct

Reverse

Select Reverse on SP1 for heating and Direct for
cooling applications.

rEu.L

Select SP1/2 LED indicator modes

SP1

SP2

[1n.2n]

Normal

Normal

1i.2n

Invert

Normal

1n.2i

Normal Invert

1i.2i

Invert Invert

SPAn [0.0]

to ±25% sensor maximum

-1999–2500 in Linear

Sensor span adjust
For recalibrating to align readings with another instrument e.g. External Meter, data logger.
See Full Operating Manual (ADVANCED SETTINGS).

ZEro

[0.0]

to ±25% sensor f/s

-1999–2500 in Linear

Zero sensor error (see Sensor span adjust above).

ChEK [oFF]

on

Select control accuracy monitor

rEAD

[

Var]

hi Lo

Read control accuracy monitor

tECh

[

Ct A]

CT b Ct 1 Ct 2 Ct 3 Ct 4 oS 1 uS oS 2

Read Autotune tuning cycle data (see Operating Manual)

UEr

Software version number

rSET

[nonE]

ALL

Resets all functions to factory settings
Caution: This selection will lose all of the current settings.

LEVEL 4

Access to level 4 is gained through

UEr

in level 3. Press and hold ▲ and ▼ for 10 seconds.

Enter level 4 at

Lock

, release ▲ and ▼ together. Display reads

LoCK nonE

Program security using

Lock [nonE]

Select from three

Lock

options: Press and hold ✱, press ▲ to index.

LEV.3

locks level 3, 4, A (and C when fitted)

LEV.2

locks level 2, 3, 4, A (and C when fitted)

ALL

locks all functions (including C when fitted)

Note: Any locked functions and options can still be read.

Press ▼ to access following functions.

Function

Options

[Factory settings] shown in brackets

ProG [Auto]

StAY

Program mode auto-exit switch
Auto-exit returns display to normal if 60 seconds of key inactivity, select StAY to disable

no.AL [oFF]

on

Disable SP2 alarm annunciator -AL-
Select on to disable -AL-

di.SS dir

1 to 32

[6]

Display sensitivity

dir

= direct display of input

1

= maximum,

32

= minimum sensitivity

dEr.S

0.1 to 1.0

[0.5]

Derivative sensitivity

SEt.L (oFF)

on

Remember next menu exit point and use as new
menu entry point, except when exit is in Level 1.

LEVEL P

See PROGRAMMER Section, page 11.

LEVEL C

COMMS SETTINGS; visible only when Comms option
fitted.

Additional in depth information on controller operation is available in the APPGUIDE.PDF
available for down load from www.cal-controls.com

LEVL 4

Will be affected by

dECP

settings in Level A

LEVEL 3 CONTINUED

LEVL P

LEVL C