10.4

CONTR: Controller

This main group determines the controller structure and function, which is used as starting point for

controller configuration for a particular application. The main controller configuration C.100 leads to

an input and output pre-adjustment (C.180.. C.190, C.500.. C591). This ‘proposal’ must always be

checked before commissioning and corrected, if necessary. After determination of this word, no

further settings are required for a large number of applications. Additional function adaptions are

possible via configuration words C.105 and the following configurations.

Main controller configuration 1:

CFunc

CType

WFunc

(Control behaviour)

(Controller type)

(Set-point function)

00: signaller 1 output

01: signaller 2 outputs

02: 2-pnt.controller

03: 3-pnt.controller

(heating switching and cooling switching)

04: 3-pnt.controller

(heating continuous and cooling switching)

05: 3-pnt.controller

(heating switching and cooling continuous)

06: {/Y-off

07: 3-pnt.stepping

08: 3-pnt.stepping with Yp (INP6)

09: continuous with position controler

10: continuous

11: continuous split-range

(only with Optin C; OUT1 and OUT3)

12: continuous with current feedback via Yp (INP6)

0: standard controller

1: ratio controller

(Ä C.107)

2: 3-element controller

x

eff

= x1+a w (x2-x3)

3: mean value

x

eff

= (1-b) w x1+b w x2

0: set-point

1: set-point / cascade

2: programmer

3: set-point with ext. offset

4: set-point / cascade with

internal offset

5: set-point / cascade with

external offset

6: programmer with

internal offset

7: programmer with

external offset

Main controller configuration 2:

CMode

CDiff

CFail

(Output action) (Differentiation)

(Controller behaviour with main variable sensor break)

0: inverse

1: direct

0: differentiate Xw

1: differentiate X

0: neutral (controller outputs switched off)

1: Ypid = Ymin (0)

2: Ypid = Ymax (100)

3: Ypid = Y2 (adjustment via front panel not possible)

4: Ypid = Y2 (adjustment via front panel possible)

Configuration

19

Operating instruction KS94