9 tune:self-tuning 32, 10 disp: user interface for operation 32, Configuration – West Control Solutions KS 94 User Manual

Page 30

Advertising
background image

10.9

TUNE:self-tuning

The type of controller self-tuning and the type of controlled self-tuning can be

adjusted!

Main configuration:

OMode

OCond

OCntr

ODP

(Controller

self-tuning)

(Process-at-rest mode)

(Controlled self-tuning mode)

(Decimals for

OCntr)

0: Standard 0: grad = 0

1: grad < 0

with inverse controller

or grad > 0

with direct controller

2: grad

0

0: no function

1: selectablecontrol/disturbance behaviour

2: switch-over via operation

3: switch-over via control input

4: switch-over controlled by Weff

5: switch-over controlled by Xeff

6: switch-over controlled by Ypid

7: switch-over controlled by X-W

0: no decimal point

1: 1 digit behind

the decimal point

2: 2 digits behind

the decimal point

3: 3 digits behind

the decimal point

10.10 DISP: User interface for operation

Configuration of display function signification via front panel

L1 process operation:

Text2

UsrTx

LED

Langu

(Signification of display text2)

(User text

selection)

(Front LED function) (Language selection

of text displays)

0: Y (correcting variable display)

bargraph (-100% ...) 0% ...+100%

1: Xw (control deviation) bargraph

-10% ... 0% ... +10% span

2: Tprog bargraph (elapsed

program time) 0 ... tmax

3: Status display

0: no user text

1: user text via

control input

2: user text via

function

statuses

0: German

1: English

2: French

0: logic output levels

Y1,Y2,LIM1,LIM2

1: logic output levels LIM1...LIM4

2: programmer control outputs D1 ... D4

3: logic output levels LIM1,Y1, Y2, LIM2

4: PROFIBUS-DP errors

5: logic output levels Y2, Y1, LIM1, LIM2

6: logic output levels LIM1,Y2, Y1, LIM2

Unit display:

LUnit

xDisp

wDisp

(Unit selection for text 1)

(select process value for disp.)

(select set-point for disp.)

00: no unit

01: °C

02: °F

03: %

04: mbar

05: bar

06: t/h

07: m3/h

08: 1/min

99: freely selectable

Engineering toolnecessary

0: Process value =xeff

1: Process value =x1

2: Process value =x2

3: Process value =x3

0: set-point disp. = Standard

1: set-point disp. = Weff

Configuration

Operating instruction KS94

32

Advertising