Easicool™ precision air conditioning, Electrical data v55cw – Airedale EasiCool 6kW 64kW User Manual

Page 115

Advertising
background image

EasiCool™

Precision Air Conditioning

Mechanical

(1)

Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water (Optional Extra) - X & WX Models

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

V55CW-EZRE-0

V55CW-EZRE-1

V55CW-EZRE-2

Unit Data Full Function

(1)

Nominal Run Amps

A

72.4

76.0

131.0

Maximum Start Amps

A

87.1

90.5

156.5

Recommended Mains Fuse Size

A

100

100

200

Unit Data Cooling Only
Nominal Run Amps

(2)

A

12.86

13.4

22.8

Maximum Start Amps

A

87.1

90.5

156.5

Recommended Mains Fuse Size

A

20

20

32

Max Mains Incoming Cable Size

mm²

35

35

185

Mains Supply

V

400V / 3PH + N / 50HZ

380V / 3PH + N / 60HZ

220V / 3PH / 60HZ

Control Circuit

VAC

24

24

24

Evaporator Fan Motor - Per Fan

AC

AC

AC

Quantity

2

2

2

Maximum Electrical Input Power

(3)

kW

3.5

3.5

3.5

Full Load Amps

A

6.18

6.43

11.14

Locked Rotor Amps

A

43.3

45.01

77.98

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

3

3

3

Number of Elements

12

12

12

Rating

kW

30

30

30

Current per Phase

A

43.30

45.58

78.73

Humidifer
Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.24

17.09

29.52

Evaporator Fan Options

Centrifugal Forward Curved Belt & Pulley AC - Designed to 25Pa ESP

Larger Fan Motor - Per Fan

AC

AC

AC

Quantity

2

2

2

Maximum Electrical Input Power

(3)

kW

4.6

4.6

4.6

Full Load Amps

A

8.12

8.12

14.45

Locked Rotor Amps

A

60.9

60.9

101.15

Standard Size Motor - EC Motor - Per Fan

Centrifugal Backward Curved DD EC - Designed to 25Pa ESP

Quantity

2

2

2

Maximum Electrical Input Power

(3)

kW

2 x 3.1

2 x 3.1

2 x 3.1

Full Load Amps

A

4.8

4.8

4.8

115

EasiCool Technical Manual 7535768 V1.2.0_02_2013

Te

ch

nic

al

Chi
lle

d W

ate

r

V

Technical Data Upflow

Electrical Data

V55CW

Advertising