Easicool™ precision air conditioning, Technical data upflow, Te ch ni ca l chi lle d w at er v – Airedale EasiCool 6kW 64kW User Manual

Page 82: Noise data

Advertising
background image

EasiCool™

Precision Air Conditioning

Sound

Overall

Frequency (Hz) dB

Measurement

dB(A)

63

125

250

500

1000

2000

4000

8000

V6CW

D A

72

66

70

68

68

68

67

59

55

R A

53

63

64

55

49

47

42

36

26

C B

53

63

64

55

49

47

42

36

26

S @ 3m

39

49

50

40

34

32

27

22

11

V8CW

D A

78

71

75

74

73

73

72

65

60

R A

59

68

70

60

54

52

47

42

31

C B

59

68

70

60

54

52

47

42

31

S @ 3m

44

54

55

45

40

38

32

27

17

V10CW

D A

81

74

78

77

76

76

75

68

63

R A

62

71

73

63

57

55

50

45

34

C B

62

71

73

63

57

55

50

45

34

S @ 3m

47

57

58

48

43

41

35

30

20

V13CW

D A

78

72

75

73

73

73

72

65

60

R A

59

69

70

60

54

52

47

41

31

C B

59

69

70

60

54

52

47

41

31

S @ 3m

44

54

55

45

39

38

32

27

17

V15CW

D A

74

71

76

73

70

69

68

63

58

R A

57

68

70

60

51

48

43

40

29

C B

57

68

70

60

51

48

43

40

29

S @ 3m

43

54

56

45

37

34

28

25

14

V17CW

D A

78

75

79

77

74

73

71

67

62

R A

61

72

74

63

55

52

46

43

33

C B

61

72

74

63

55

52

46

43

33

S @ 3m

47

58

59

49

40

37

32

29

18

V20CW

D A

82

75

79

78

77

78

76

69

64

R A

63

73

74

64

58

56

51

46

35

C B

63

73

74

64

58

56

51

46

35

S @ 3m

48

58

59

50

44

42

37

31

21

V22CW

D A

82

75

79

78

77

78

76

69

64

R A

63

73

74

64

58

56

51

46

35

C B

63

73

74

64

58

56

51

46

35

S @ 3m

48

58

59

50

44

42

37

31

21

V26CW

D A

86

80

84

82

81

82

80

73

68

R A

67

77

78

68

62

61

55

50

40

C B

67

77

78

68

62

61

55

50

40

S @ 3m

53

62

64

54

48

46

41

35

25

Technical Data Upflow

Noise Data

Key:
D A

= Discharge Air Sound Power

R A

= Return Air Sound Power

C B

= Case Breakout Sound Power

S @ 3m

= Sound Pressure at 3m

(1)

dB(A) is the overall sound level, measured on the A scale.

(2)

All sound data measured at nominal conditions.

The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.

82

EasiCool Technical Manual 7535768 V1.2.0_02_2013

Te

ch

ni

ca

l

Chi

lle

d W

at

er

V

Advertising