Easicool™ precision air conditioning, Technical data downflow, Te ch nic al chi lle d w ate r df – Airedale EasiCool 6kW 64kW User Manual

Page 41: Performance data, Operating limits

Advertising
background image

EasiCool™

Precision Air Conditioning

Technical Data Downflow

Performance Data

Cooling Capacity (1)

Chilled Water Inlet/Outlet °C

Air On

5/10°C

7/12°C

8/14°C

10/16°C

(DB°C/%RH)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

DF28CW-EZRE

22/50

36.9

29.1

28.6

25.5

22.5

22.5

18.3

18.3

24/45

42.7

34.2

34.2

30.5

27.5

27.5

23.2

23.2

26/40

48.1

39.5

39.3

35.7

32.7

32.7

28.4

28.4

DF31CW-EZRE

22/50

41.6

32.9

32.3

28.8

25.4

25.4

20.6

20.6

24/45

48.2

38.6

38.6

34.4

31.1

31.1

26.3

26.3

26/40

54.4

44.7

44.5

40.3

37.0

37.0

32.1

32.1

DF35CW-EZRE

22/50

48.7

38.5

37.8

33.7

29.7

29.7

24.1

24.1

24/45

56.7

45.5

45.4

40.5

36.6

36.6

30.9

30.9

26/40

64.3

52.8

52.6

47.7

43.7

43.7

37.9

37.9

DF40CW-EZRE

22/50

52.0

42.6

38.7

35.6

32.3

32.3

26.0

26.0

24/45

63.2

53.4

47.6

44.6

39.8

39.8

33.5

33.5

26/40

68.4

58.1

54.2

50.4

47.6

47.6

41.1

41.1

DF45CW-EZRE

22/50

55.3

45.3

41.1

37.9

34.4

34.4

27.7

27.7

24/45

67.1

56.7

50.6

47.4

42.3

42.3

35.6

35.6

26/40

72.6

61.6

57.5

53.5

50.4

50.4

43.6

43.6

DF50CW-EZRE

22/50

56.9

47.8

41.7

41.7

35.7

35.7

28.3

28.3

24/45

66.8

56.6

51.3

49.1

44.4

44.4

37.1

37.1

26/40

79.8

70.7

59.3

59.3

53.4

53.4

46.0

46.0

DF55CW-EZRE

22/50

63.3

50.9

48.2

44.3

38.3

38.3

30.5

30.5

24/45

74.0

60.1

58.5

53.4

47.5

47.5

39.8

39.8

26/40

84.1

69.8

68.0

62.9

57.0

57.0

49.3

49.3

DF60CW-EZRE

22/50

68.3

54.9

52.0

47.8

41.3

41.3

32.9

32.9

24/45

79.7

64.8

63.0

57.5

51.2

51.2

42.9

42.9

26/40

90.5

75.2

73.3

67.8

61.4

61.4

53.0

53.0

TC = Total Cooling SC = Sensible Cooling

(1)

All data quoted is gross.

(2)

Deduct fan motor gain for nett duties, refer to

Mechanical Data

.

(3)

Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to

Ethylene Glycol Correction Factors

.

(4)

Refer to

Waterside Pressure Drop (kPa)

.

Operating Limits

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55% (based upon 24°C Dry Bulb)

Water Entering Temperature

+5°C to +10°C

Water Leaving Temperature

+10°C to +16°C

(1)

Conditions quoted at 100% Water.

(2)

For conditions outside those quoted, please refer to Airedale.

41

EasiCool Technical Manual 7535768 V1.2.0_02_2013

Te

ch

nic

al

Chi
lle

d W

ate

r

DF