EasiCool™

Precision Air Conditioning

Technical Data

Nominal Design Operating Condition 24°C Dry Bulb 45% RH

IMPORTANT

Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling capacity requirements.
Fan Power Input can be found in the mechanical data sections.
Fan Power Input is taken at the operating conditions based on 25Pa ESP.

Te

ch

nic

al

39

EasiCool Technical Manual 7535768 V1.2.0_02_2013

Chi
lle

d W

ate

r

DF

Operating Limits

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55% (Based upon 24°C Dry Bulb)

Water Entering Temperature

+5°C to +10°C

Water Leaving Temperature

+10°C to +16°C

Moisture Content