Easicool™ precision air conditioning, Technical data downflow, Te ch ni ca l df chi lle d w at er – Airedale EasiCool 6kW 64kW User Manual

Page 40: Performance data, Operating limits

Advertising
background image

EasiCool™

Precision Air Conditioning

Technical Data Downflow

Performance Data

Cooling Capacity (1)

Chilled Water Inlet/Outlet °C

Air On

5/10°C

7/12°C

8/14°C

10/16°C

(DB°C/%RH)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

DF6CW-EZRE

22/50

8.2

6.6

6.2

5.8

5.0

5.0

3.9

3.9

24/45

9.7

7.9

7.6

7.0

6.2

6.2

5.2

5.2

26/40

11.1

9.3

8.9

8.3

7.5

7.5

6.5

6.5

DF8CW-EZRE

22/50

10.6

8.6

8.0

7.5

6.4

6.4

5.1

5.1

24/45

12.4

10.1

9.7

8.9

7.9

7.9

6.7

6.7

26/40

14.0

11.7

11.2

10.5

9.5

9.5

8.2

8.2

DF10CW-EZRE

22/50

12.7

10.3

9.6

9.0

7.7

7.7

6.1

6.1

24/45

14.8

12.1

11.7

10.7

9.5

9.5

8.0

8.0

26/40

16.8

14.0

13.5

12.6

11.4

11.4

9.8

9.8

DF13CW-EZRE

22/50

15.6

12.4

11.9

10.8

9.4

9.4

7.5

7.5

24/45

18.4

14.8

14.7

13.2

11.8

11.8

9.9

9.9

26/40

21.2

17.4

17.2

15.7

14.3

14.3

12.4

12.4

DF15CW-EZRE

22/50

18.5

14.7

14.1

12.8

11.1

11.1

8.9

8.9

24/45

21.5

17.3

17.1

15.3

13.7

13.7

11.5

11.5

26/40

24.3

20.0

19.8

18.0

16.4

16.4

14.2

14.2

DF17CW-EZRE

22/50

20.8

16.6

15.9

14.4

12.5

12.5

10.0

10.0

24/45

24.2

19.5

19.2

17.3

15.5

15.5

13.0

13.0

26/40

27.4

22.5

22.3

20.3

18.5

18.5

16.0

16.0

DF20CW-EZRE

22/50

23.5

18.8

17.9

16.4

14.2

14.2

11.3

11.3

24/45

27.6

22.3

21.8

19.8

17.7

17.7

14.9

14.9

26/40

31.4

26.0

25.5

23.5

21.3

21.3

18.4

18.4

DF22CW-EZRE

22/50

25.3

20.5

18.7

16.9

15.5

15.5

12.4

12.4

24/45

29.7

24.3

23.4

21.6

19.2

19.2

16.1

16.1

26/40

33.8

28.3

26.5

24.1

23.1

23.1

20.0

20.0

DF26CW-EZRE

22/50

29.2

23.7

21.6

19.5

17.8

17.8

14.3

14.3

24/45

34.1

27.9

26.9

24.8

22.1

22.1

18.5

18.5

26/40

38.7

32.4

30.5

27.6

26.5

26.5

22.9

22.9

TC = Total Cooling SC = Sensible Cooling

(1)

All data quoted is gross.

(2)

Deduct fan motor gain for nett duties, refer to

Mechanical Data

.

(3)

Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to

Ethylene Glycol Correction Factors

.

(4)

Refer to

Waterside Pressure Drop (kPa)

.

Operating Limits

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55% (based upon 24°C Dry Bulb)

Water Entering Temperature

+5°C to +10°C

Water Leaving Temperature

+10°C to +16°C

(1)

Conditions quoted at 100% Water.

(2)

For conditions outside those quoted, please refer to Airedale.

40

EasiCool Technical Manual 7535768 V1.2.0_02_2013