Using the multi-inputs – Kaman 8000 Enclosures User Manual

Page 35

Advertising
background image

35

Using the Multi-Inputs


Select the input you wish to display by turning the front panel selector switch. The knob's
index mark indicates the selected input as labeled on the front panel lens.



fig. 21 -- MCD 8000 Front Panel;




The display is normally configured to display the measuring channel output in the numbered
position starting to the right of the display. For example, if you wish to read the output from

channel 4 you will need to set the display switch to `4' which will read the output from the
module 4 positions to the right of the display. Some function card modules contain dual channel
outputs, these modules will count as 2 positions.
For example, if you had 2 measuring

channels, a dual RMS->DC converter card (dynamic module -004), and a third measuring
channel in the fourth slot, when the display switch is on channel 4 you will read the RMS
output of channel 2 and if the switch is on channel 5 you will read the measuring channel in

the fourth position to the right of the display. Some modules have no outputs that go to the
display, these modules count as 0 positions.
The following table gives the displayed outputs
and count. The channel numbers are relative to the modules to the left of the function card.


Dash

Displayed

1st

2nd

Module number Outputs Position

8200

any

1

----

----

8200HT any

1

----

----

VC8000 any

0

----

----

SP8000 any

0

----

----

SC8000 any

1

Summed

Output

----

DY8000 -001

2

Ch

1

P-P

Ch

1

RMS

DY8000 -002

2

Ch

1

+Peak

Ch

2

+Peak

DY8000 -003

2

Ch

1

-Peak

Ch

2

-Peak

DY8000 -004

2

Ch

1

RMS

Ch

2

RMS

Table 4 -- Displayed Outputs;