In order to purge air in water pipes within a closed‐loop system, an air vent 

and air separator should be installed in to the system.  Required circulation 
flow  rates  are  labeled  next  to  each  application  diagram.    These  flow  rate 
requirements must be followed. 

 Toxic chemicals used in boiler treatments such as alcohol, glycerol and glycol 

groups must not be introduced into the system if the system incorporates an 
open‐loop potable water system. 

 The water heater can be used to supply potable water and space heating and 

shall  not  be  connected  to  any  heating  system  or  component(s)  previously 
used with non‐potable water where any chemicals were added to the water 
heating appliances. 

 When the system requires water for space heating at temperatures higher 

than  required  for  other  uses,  a  means  such  as  a  mixing  valve  shall  be 
installed to temper the water for those other uses in order to reduce scald 
hazard potential. 

 Water  temperature  over  125°F  (52°C)  can  cause  severe  burns  instantly  or 

death from scalds. 

 Chemicals such as diluted Glycol can be used for radiant floor, Hydro/fan coil 

air  or  Baseboard  heating  only.  The  diluted  solution  of  glycol  must  contain 
between 25 and 55 % of Glycol. Be aware that in closed‐loop glycol systems, 
low  pressure  in  the  heat  exchanger  can  cause  low‐temperature  boiling, 
resulting  in  excessive  noise  and  damage  to  the  water  heater.  Consult  with 
the glycol maker for specifications prior to use.    

This is a concept drawing only. 

APPLICATIONS

 

‐Space‐Heating Applications‐ 





























 













* The recirculation pump is to be controlled by:
‐Dual‐set aquastat (recommended w/timer) 

OR 

‐“Pump Control Connections” 510 (T‐D2) models only. 
Refer to p. 23.
 
* The recirculation pump is to provide no less than 2 
GPM and no more than 4 GPM through each 
activated unit in the system. 

‐Recirculation‐ 

WARNING 

Pressure 
relief valve

Check valve

Check valve

Air 
separator

Recirculation 
pump 

Hot water outlet to 
fixtures 

Air Vent

Unions 

Gas supply 

Ball valves 

Expansion tank

Y‐Strainer 

Cold water 
inlet 

Hot
Water
Outlet

S

Cold
Water
Inlet

Gas
Inlet