6.3 Composition of an RTU request message (transmitted from a high-level computer

to this product)

For codes a) through i), see "6.5 Description of RTU codes."

6.3.1 Composition of a read request message

a) Slave address

1BH

b) Function code

03H

c) Register address

High level

00H

First register address

Low level

00H

d) Number of registers

High level

00H

Fixed at 2

Low level

02H

e) CRC-16

Low level

31H

High level

C6H

6.3.2 Composition of a write request message

a) Slave address

03H

b) Function code

10H

c) Register address

High level

00H

First register address

Low level

C0H

d) Number of registers

High level

00H

Fixed at 2

Low level

02H

f) Number of data items

04H

Number of registers 2

g)

Data for the first register

(a low-level word)

High level

00H

When writing ①, ②, ③, and ④

H in the data, write them in the

order described on the left-hand

side. (① represents 1 byte.)

Low level

6FH

Data for the first register + 1

(a high-level word)

High level

00H

Low level

00H

e) CRC-16

Low level

5AH

High level

C4H

6.3.3 Composition of a store request message

a) Slave address

03H

b) Function code

10H

c) Register address

High level

02H

First register address

Low level

0EH

d) Number of registers

High level

00H

Fixed at 2

Low level

02H

f) Number of data items

04H

Number of registers 2

g)

Data for the first register

(a low-level word)

High level

00H

The data about the storage of settings is

arbitrary.

Low level

00H

Data for the first register + 1

(a high-level word)

High level

00H

Low level

00H

e) CRC-16

Low level

FBH

High level

60H


Advertising