1 composition of a read request message, 2 composition of a write request message – TOHO ELECTRONICS TTM000 User Manual
Page 27
27
6.8 Composition of an ASCII request message
(transmitted from a high-level computer to this product)
For the codes a) through g), see "6.10 Description of ASCII codes."
6.8.1 Composition of a read request message
a) Start code
“:”
b) Slave address
“1” , “B”
c) Function code
“0” , “3”
d) Register address
High level
“0” , “0”
First register address
Low level
“0” , “0”
e) Number of registers
High level
“0” , “0”
Fixed at 2
Low level
“0” , “2”
f) LRC
“E” , “0”
g) End code
CR, LF
6.8.2 Composition of a write request message
a) Start code
“:”
b) Slave address
“0” , “3”
c) Function code
“1” , “0”
d) Register address
High level
“0” , “0”
First register address
Low level
“C” , “0”
e) Number of registers
High level
“0” , “0”
Fixed at 2
Low level
“0” , “2”
h) Number of data items
“0” , “4”
Number of registers 2
i)
Data for the first register
(a low-level word)
High level
“0” , “0”
③
When writing ①, ②, ③, and ④
H in the data, write them in the
order described on the left-hand
side. (① represents 1 byte.)
Low level
“6” , “F”
④
Data for the first register + 1
(a high-level word)
High level
“0” , “0”
①
Low level
“0” , “0”
②
f) LRC
“E” , “0”
g) End code
CR, LF