1 composition of a read request message, 2 composition of a write request message – TOHO ELECTRONICS TTM000 User Manual

Page 27

Advertising
background image

27

6.8 Composition of an ASCII request message

(transmitted from a high-level computer to this product)

For the codes a) through g), see "6.10 Description of ASCII codes."

6.8.1 Composition of a read request message

a) Start code

“:”

b) Slave address

“1” , “B”

c) Function code

“0” , “3”

d) Register address

High level

“0” , “0”

First register address

Low level

“0” , “0”

e) Number of registers

High level

“0” , “0”

Fixed at 2

Low level

“0” , “2”

f) LRC

“E” , “0”

g) End code

CR, LF


6.8.2 Composition of a write request message

a) Start code

“:”

b) Slave address

“0” , “3”

c) Function code

“1” , “0”

d) Register address

High level

“0” , “0”

First register address

Low level

“C” , “0”

e) Number of registers

High level

“0” , “0”

Fixed at 2

Low level

“0” , “2”

h) Number of data items

“0” , “4”

Number of registers 2

i)

Data for the first register

(a low-level word)

High level

“0” , “0”

When writing ①, ②, ③, and ④

H in the data, write them in the

order described on the left-hand

side. (① represents 1 byte.)

Low level

“6” , “F”

Data for the first register + 1

(a high-level word)

High level

“0” , “0”

Low level

“0” , “0”

f) LRC

“E” , “0”

g) End code

CR, LF