8. Connections

Host Computer

(Master Station)

Unit1

(Slave Station)

Unit2

(Slave Station)

Unit3

(Slave Station)

A(+)

B(-)

A(+)

B(-)

A(+)

B(-)

A(+)

B(-)

terminating

resistor

terminatin

g resistor

Cable①

Cable②

Cable③

Above drawing shows example of connecting 1 to 3 slave stations to a master station.

Use cables with the same characteristic impedance for cables ① to ③.

- For slave station nos. 1 to 3, connect them dependently as shown in the drawing.

The same characteristic impedance cables are used for the connections between

the slave stations.

Attach terminating resistor to both the master station side ① and the farthest ② ones among the

slave stations (no. 3).

Make sure to select terminating resistor in order that the [Characteristic Impedance from cables ①

to ③] = [Resistance Value of ①] = [Resistance Value of ②]

- Furthermore, use characteristic impedance cable whose [Resistance Value of ①] // [Resistance

Value of ②] (parallel combination resistance value) becomes above 75-ohms.