TOHO ELECTRONICS TTM000 User Manual

Page 38

Advertising
background image

38

Identifier Relative

address

Absolute

address

Character

Name

R/W

Description

□MD

0028h

40041

Control mode setting

R/W R/W the control mode setting

Control execution: 00000

Manual control: 00001

Control stop: 00002

Auto-tuning in progress: 00003

CNT

002Ah

40043

Selection of control type setting

R/W R/W the control type setting

DIR

002Ch

40045

Change of normal or reverse

R/W R/W the forward/reverse operation

switchover setting

MV1

002Eh

40047

Manipulated value

for output 1

R/W R/W the output 1 operation amount

TUN

0030h

40049

Set for PID tuning type

R/W R/W the tuning type setting

ATG

0032h

40051

AT coefficient setting

R/W R/W the AT factor

ATC

0034h

40053

AT sensitivity setting

R/W R/W the AT sensitivity

□P1

0036h

40055

Proportional band setting

for output 1

R/W R/W the output 1 proportional band setting

□I1

0038h

40057

Integral time setting

R/W R/W the integral time setting

□D1

003Ah

40059

Derivative time setting

R/W R/W the derivative time setting

□T1

003Ch

40061

Proportional cycle setting

For output 1

R/W R/W the output 1 proportional frequency

setting

ARW

003Eh

40063

ARW(Anti-reset windup) setting

R/W R/W the anti-reset windup

MH1

0040h

40065

High limit setting of manipulated

value for output 1

R/W R/W the amount-of-operation limiter upper

limit setting

ML1

0042h

40067

Low limit setting of manipulated

value for output 1

R/W R/W the amount-of-operation limiter lower

limit setting

□C1

0044h

40069

Control sensitivity setting

for output 1

R/W R/W the output 1 control sensitivity setting

CP1

0046h

40071

OFF position setting for output 1

R/W R/W the output 1 off-point position setting

MV2

0048h

40073

Manipulated value for output 2

R/W R/W the output 2 operation amount

□P2

004Ah

40075

Proportional band setting

for output 2

R/W R/W the output 2 proportional band setting

□T2

004Ch

40077

Proportional cycle setting for

output 2

R/W R/W the output 2 proportional frequency

setting

MH2

004Eh

40079

High limit setting of manipulated

value for output 2

R/W R/W the amount-of-operation limiter upper

limit setting

ML2

0050h

40081

Low limit setting of manipulated

value for output 2

R/W R/W the amount-of-operation limiter lower

limit setting

□C2

0052h

40083

Control sensitivity setting

for output 2

R/W R/W the output 2 control sensitivity setting

CP2

0054h

40085

OFF position setting

for output 2

R/W R/W the output 2 off-point position setting

PBB

0056h

40087

Manual reset setting

R/W R/W the manual reset

□DB

0058h

40089

Dead band setting

R/W R/W the dead band setting

RP1

005Ah

40091

SV Ramp variation setting

R/W R/W the SV lamp time setting

RP2

005Ch

40093

SV2 Ramp variation setting

R/W R/W the SV2 lamp time setting

E1F

005Eh

40095

Function setting for EV1

R/W R/W the PV event output 1 function setting

E1H

0060h

40097

High limit setting for EV1

R/W R/W the event output 1 upper limit setting

E1L

0062h

40099

Low limit setting for EV1

R/W R/W the event output 1 lower limit setting

E1C

0064h

40101

Control sensitivity setting

for EV1

R/W R/W the event output 1 sensitivity setting

E1T

0066h

40103

Delay time setting for EV1

R/W R/W the event output 1 delay timer setting

Advertising