39

Identifier Relative

address

Absolute

address

Character

Name

R/W

Description

E1B

0068h

40105

Abnormal for EV1

R/W R/W the special event output 1 function

setting

E1P

006Ah

40107

Polarity setting for EV1

R/W R/W the event output 1 polarity setting

CM1

006Ch

40109

CT input monitor for EV1

R

Read the CT input monitor

CT1

006Eh

40111

Abnormality current value of heater

for EV1

R/W R/W the event output 1 current abnormality

setting

E2F

0070h

40113

Function setting for EV2

R/W R/W the PV event output 2 function setting

E2H

0072h

40115

High limit setting for EV2

R/W R/W the event output 2 upper limit setting

E2L

0074h

40117

High limit setting for EV2

R/W R/W the event output 2 lower limit setting

E2C

0076h

40119

Control sensitivity setting

for EV2

R/W R/W the event output 2 sensitivity setting

E2T

0078h

40121

Delay time setting for EV2

R/W R/W the event output 2 delay timer setting

E2B

007Ah

40123

Abnormal for EV2

R/W R/W the special event output 2 function

setting

E2P

007Ch

40125

Polarity setting for EV2

R/W R/W the event output 2 polarity setting

CM2

007Eh

40127

CT input monitor for EV2

R

Read the CT input monitor

CT2

0080h

40129

Abnormality current value of heater

for EV2

R/W R/W the event output 2 current abnormality

setting

DIF

0082h

40131

Function setting for DI

R/W R/W the DI input function setting

DIP

0084h

40133

Polarity setting for DI

R/W R/W the DI polarity setting

SV2

0086h

40135

Setting for SV2

R/W R/W the control setting 2

PRT

0088h

40137

Communications protocol setting

R/W R/W the communications protocol setting

Special-purpose protocol: 00000

MODBUS (RTU): 00001

MODBUS (ASCII): 00002

COM

008Ah

40139

Parameter setting for communication R/W R/W the communications parameter setting

Example: □B8N2

BPS

008Ch

40141

Speed setting

R/W R/W the communications speed setting

Example: 00096 (if 9600 bps)

ADR

008Eh

40143

Address setting

R/W R/W the communications address setting

AWT

0090h

40145

Response delay time setting

R/W R/W the response delay setting

MOD

0092h

40147

Mode selection setting

R/W R/W the communications mode switchover

setting

RO: 00000

RW: 00001

TMO

0094h

40149

Timer output setting

R/W R/W the timer output destination setting

TMF

0096h

40151

Timer function setting

R/W R/W the timer function setting

H/M

0098h

40153

Timer unit selection

R/W R/W the timer unit switchover setting

TSV

009Ah

40155

Timer SV start permissible range

R/W R/W the timer SV start tolerance setting

TIM

009Ch

40157

Timer time setting

R/W R/W the timer time setting

TIA

009Eh

40159

Timer residual time monitor setting

R

Read the timer remaining time monitor

TRF

00A0h

40161

Transfer output function setting

R/W R/W the transmission output function setting

Advertising