5 rack mounting, Rack mounting – ADC 70 User Manual

Page 22

Advertising
background image

ADCP-80-524 • Issue 1 • November 2001

Page 22
©

2001, ADC Telecommunications, Inc.

Figure 15. Cable Management Bar Installation (Uninterrupted Power Fuse Panel Shown)

4.5

Rack Mounting

The

fuse panel can be mounted in either a 19- or 23-inch (48.26 or 58.42 cm) wide rack. Two

sets

of mounting brackets, one set for 19-inch racks and one set for 23-inch racks, are provided

with

the fuse panel. Eight 5/16-inch (7.94 mm) long, thread-forming, Phillips-drive, 8-32 flat-

head

screws are provided for attaching the mounting brackets to the panel. Four 3/8-inch (9.53

mm)

long, Phillips-drive, 12-24 pan-head screws (with #12 flat washers) are provided for

attaching

the mounting brackets to the equipment rack.

Use

the following procedure to install the fuse panel in the equipment rack:

1. Select

the set of mounting brackets (19- or 23-inch) that correspond to the width of the

equipment

rack into which the fuse panel will be installed.

2. Orient

the mounting brackets as shown in

Figure 16

.

3. Attach

the brackets to the sides of the fuse panel chassis using the eight 5/16-inch (7.94

mm)

flathead screws provided. Tighten screws to 15 pound force-inches (1.7 Newton

meters)

of torque to insure grounding.

4. Place

the fuse panel in the specified mounting space within the rack.

5. Secure

the panel to the rack as shown in

Figure 17

using the four 3/8-inch (9.525 mm)

long

pan-head screws and flat washers provided.

Caution:

When attaching the cable management bar to the fuse panel, use only the hardware

supplied

with the cable management bar. Use of any other hardware could cause contact with

internal

parts of the fuse panel. If parts are missing, please contact ADC.

Note:

A fuse panel with the cable management bar attached may exceed the 12-inch

(3.05 mm)

overall depth objective described in GR-63 CORE, 02-14.

Caution:

When attaching the mounting brackets to the fuse panel, use only the 5/16-inch (7.94

mm)

long, black chromate finish, thread forming, flathead screws provided with the panel. Use

of

any other hardware could cause contact with internal parts of the panel. If parts are missing,

contact

ADC to order replacement parts.

16387-B

CABLE

MANAGEMENT

BAR

ATTACH TO

EITHER SET
OF 3 HOLES

MOUNTING BRACKET

INSTALLED FOR

19-IN. (48.26 CM)

RACK MOUNTING

Advertising