10 input power connectors, Figure 21 – ADC 70 User Manual

Page 27

Advertising
background image

ADCP-80-524 • Issue 1 • November 2001

Page 27

©

2001, ADC Telecommunications, Inc.

Figure 21. Wire Wrap Alarm Contact Connection

4.10 Input Power Connectors

Connect

the input power wires to the input power connectors labeled “BATT” and connect the

return

wires to the return connectors labeled “RTN” for both buses in the fuse panel as shown in

Figure 22

.

Connect input power to the appropriate power sources in accordance with applicable

local

electrical codes and/or National Electrical Codes but do not apply power to the panel

until

directed to do so.

• Compression

lug connectors: Use the included 2-hole lugs with #6 AWG copper wire

(insulation

stripped back) or optional 2-hole lugs available as accessories with appropriate

AWG

copper wire. Tighten the nuts to approximately 16 pound-force inches (1.8 Newton

meters).

Note:

Before connecting the input or output power wires, measure the resistance at each

bus

input connector as specified in

Subsection 5.2,

Resistance Test

.

Caution:

Connect only the input voltage wire [the wire labeled BATTERY or BATT, or labeled

with

the negative () voltage polarity and/or the voltage value] to the connector on the fuse

panel

labeled BATT (battery). Connect only the input return wire [the wire labeled RTN,

RETURN,

or BATTERY GROUND, or labeled with the positive (+) voltage polarity] to the

connector

on the fuse panel labeled RTN (return).

Caution:

Caution should be taken to not reverse input wires to the fuse panel. Within the fuse

panel,

the internal battery (negative voltage) wiring is protected and the internal return wiring

is

not protected by fuses. If the wires are reversed, voltage could be present on the fuse panel

chassis

and current could flow through the unprotected return wiring in the fuse panel. This

condition

can cause damage to equipment in the frame in which the fuse panel is installed and

to

equipment in adjacent frames

16161-B

CONNECT TO

APPROPRIATE

TERMINALS

OF ALARMS

CONNECT TO

APPROPRIATE

TERMINALS

OF ALARMS

WRAP TERMINAL BLOCK PINS USING #22 TO #26 AWG COPPER WIRE WITH INSULATION STRIPPED BACK.