4.8

Output Power Connectors

Connect

the output BATT and RTN terminals for each fuse circuit on each set of terminal strips

as

follows (see

Figure 20

):

• Screw-down

barrier terminal strip: Use #12 to #22 AWG wire. Wire leads should be

equipped

with crimp-on spade lugs or ring connectors that have a maximum width of

0.325

inches (8.255 mm).

The

terminals also accommodate copper wire without lugs (insulation stripped back).

Torque

the screws to approximately 9 pound-force inches (1 Newton meter).

• Set

screw barrel terminal strip: Use #12 to #24 AWG wire with insulation stripped back.

Tighten

the screws to approximately 4.5 pound-force inches (1 Newton meter).

Figure 20. Output Connector Connection (Screw-Down Barrier Terminal Strip Connectors Shown)

4.9

External Alarm Contact Connectors

Connect

each set of external alarm contacts to a local alarm system as required (see

Figure 21

).

Wrap

terminal block pins using #22 to #26 AWG copper wire with insulation stripped back.

Note:

Before connecting the output or input power wires, measure the resistance of each

bus

input connector as specified in

Subsection 5.2,

Resistance Test

.

Caution:

For screw-down barrier terminal strip outputs, use #12 AWG wire to prevent

personnel

contact with the voltages (NEBs standard, Class A2).

CONNECT USING CRIMP-ON SPADE LUGS OR RING CONNECTORS THAT HAVE A MAXIMUM WIDTH OF 0.325 IN.
(8.255 MM) ON #12 TO #22 AWG WIRE OR USING #12 TO #22 AWG WIRE WITH INSULATION STRIPPED BACK.

TORQUE THE SCREWS TO APPROXIMATELY 9 POUND-FORCE INCHES (1 NEWTON METER).

16766-A

CONNECT TO OUTPUT POWER CIRCUITS

CONNECT TO OUTPUT RETURN CIRCUITS