Connecting electric dryers (cont.)

USA only

four-wire connection for electric dryers: direct wire

• A 4-wire connection is required for all mobile and manufactured

home installations, as well as all new construction after January 1,

1996.

• A UL-listed strain relief is required.

1. Remove 5 inches (12.7 cm) of the outer covering from the wire.

Remove 5 inches of insulation from the ground wire. Cut off

approximately 1

1

⁄₂ inches (3.8 cm) from the other three wires

and strip 1 inch (2.5 cm) insulation from each wire. Bend the

ends of the three shorter wires into a hook shape.

2. Remove the terminal block access cover on the upper back of

the dryer. Install a UL-listed strain relief into the power cord

through-hole; then thread the power cable prepared in Step 1

through the strain relief.

• Use UL-listed 4-wire #10 AWG-minimum copper conductor

cable.

• Allow at least 5 ft. (1.5 m) length to allow for removal and

reinstallation of the dryer.

3. Transfer the dryer’s ground wire from behind the green ground

screw to the center screw of the terminal block. Attach the two

hot leads of the power cable to the outer terminal block screws.

Attach the white neutral wire to the center terminal block

screw. Attach the power cable ground wire to the green ground

screw. TIGHTEN ALL SCREWS SECURELY. Reinstall the terminal

block access cover.

Ground Wire

5"

(12.7 cm)

1" (2.5 cm)

UL-Listed

Strain Relief

UL-Listed

4-Wire Power

Cord

Terminal

Block

w

WarnInG

Connect the power cord to the terminal block. Each

colored wire should be connected to same color screw.

Wire color indicated on manual is connected to the same

color screw in block. Failure to follow these instructions

may result in a short or overload.

Grounding through the neutral conductor is prohibited

for: (1) new branch-circuit installations, (2) mobile homes,

(3) recreational vehicles, and (4) areas where local codes

prohibit grounding through the neutral conductor.

Neutral

(White)

Hot

(Black)

Hot

(Red)

Power Cord

Ground Wire

Ground

Screw

White Wire

moved from

Ground Screw