User's Guide ______________________________________________________________________

44 ___________________________________________________________________M210822EN-A

Typical commands:

SETALR ACTIVE 1 (activate the alarm functionality)

SETALR DIR 60 (alarm if wind vane stuck for 60 seconds)

SETALR SPD 60 (alarm if anemometer stuck for 60 seconds)

SETALR CALM 1440 (alarm if both sensors stuck for 1440 minutes)

Example:

>setalr active 1

ACTIVE= 1

DIR= 60

SPD= 60

CALM= 1440

DIRLIMIT= 3

SPDLIMIT= 0.0

>

SERVICE TIMEOUT

The SERVICE TIMEOUT command configures the timeout period of
the auto-close function of the service connection. If no data is input
within the configured time interval, the connection will close itself and
the device returns it normal operational state.

Zero value disables the auto-close function, which means that the
service connection will never close unless explicitly closed using the
CLOSE command.

SERVICE TIMEOUT <value><cr>

Example:

>service timeout 5

TIMEOUT=5

>

where

value

= The value of the service timeout, range 0 ... 30 min (default

5 min).