Chapter 3: Programming

Installation and Maintenance Manual

18

PROGRAMMING AND MONITORING

To monitor press stopping time, depress CIR# - 174 - ENT. Stopping time will be displayed in milli-

seconds from 001 to 999. Three decimal points indicate a stopping time in milliseconds, a single

decimal point, two places to the left, will indicate a stopping time in seconds to one hundredth of a

second. If the customer’s preset stopping time is exceeded, the display and decimal(s) will flash. They

will continue to flash until the brake monitor output has been reset.

To monitor press stopping angle, depress CIR# - 175 - ENT. Stopping distance will be displayed in

degree increments. If the stopping time is exceeded while in the stopping angle mode, the display will

flash. It will continue to flash until the brake monitor relay has been reset.

When operating in either of the above modes, the display will maintain the stopping data until initiation of

the next timing cycle. At this point, the display will indicate dashes until new data is available. Depres-

sion of the POS or RPM keys will return the display from this operating mode.

To program the maximum acceptable stopping time, depress CIR# - 173 - ENT. The time data can be

programmed from 001 to 999 milliseconds. If the programmed stopping time is exceeded, the brake

monitor output (LS6) will de-energize until the fault check input is opened and then closed again.

NOTE: If you are using the fault check option, the fault check relay will cycle OFF/ON when the

brake fault output is reset.