19

Installation and Maintenance Manual

Chapter 3: Programming

Programming the Maximum Stopping Time

A)

Unit must be in the Program mode.

B)

Depress

This sets the maximum allowable stopping time in .001 second intervals. If the time required to

stop following the loss of the brake monitor contact exceeds the brake monitor stopping time,

then the error output LS6 is de-energized.

Display of Stopping Time

A)

Depress

. The display will sample and hold the stopping

time of each press stroke. The stopping time is displayed in milliseconds. A single decimal in

the left-most position will indicate that a stopping time is in seconds. The display will flash when

the brake monitor stopping time (CIR# 173) has been exceeded. The display will stop flashing

when the error is reset with the fault check input. Exiting this mode is done only by pressing the

RPM/POS key. No values may be entered.

Display of Stopping Angle

A)

Depress

. The display will sample and hold the number

of degrees traveled after initiation of the brake command. The stopping distance is the distance

traveled since the loss of the contact. The display will flash when the brake monitor stopping

time (CIR# 173) has been exceeded. The display will stop flashing when the error is reset with

the fault check input. Exiting this mode is done only by pressing the RPM/POS key.

No values may be entered.

ENT

CIR# - 1 - 7

3

-

-

Maximum Stopping Time

-

ENT

-

ENT

CIR# - 1 - 7

4

-

-

ENT

CIR# - 1 - 7

3

-

-