Chapter 3: programming, Security input, Initialization – AMETEK 1995L Micro-Set PLS User Manual

Page 9: Scale factor

Advertising
background image

5

Installation and Maintenance Manual

Chapter 3: Programming

Chapter 3: Programming

3.1: Security Input

The security input is often referred to as the “Run/Program” input. This input is located on the 16-place

terminal strip and is discussed in Chapter 6: Security Inputs. This input prevents unauthorized changes

to the programmed functions. With the unit in the “Program” mode, all functions of the controller can be

programmed. With the unit in the “Run” mode, all setpoints, reset-to-preset, motion detect and other

operational functions can be verified, but the programmed information cannot be changed.

3.2: Initialization

The following key commands should be entered on the

keypad to clear all programmed data upon installation and PRIOR to programming. This sequence

clears all programmed data. All operating parameters must be reprogrammed after using this initializa-

tion function.

3.3: Scale Factor

NOTE: Programming of the desired scale factor or the number of outputs will delete all programmed

data held in memory. Therefore, these should be the first steps in your setup procedure.

The 1995L Valid Scale Factors are 2 to 1,000.

To program the scale factor, the following procedures must be followed:

1) Unit must be in the “Program” mode.

2) Depress

- Desired Scale Factor -

NOTE: Display will read from 0 to 1 less than Scale Factor.

ENT

CIR# - 9 - 9

5

-

-

ENT

CIR# - 1 - 8

0

-

-

ENT