TX312 Transmitter

TABLE 5.2-5. P127 Command 3: Initiate Random Transmission

In Loc Contents

1 Result

Code

Random message channel and repeat interval must be enabled in the TX312
configuration. If random messages have not been enabled, command 3 will
fail. If the GPS acquisition fails, the random transmission will fail. Command
3 will pull the TX312 off line. After the random transmission attempt, the
TX312 must be put back on line with command 6. When command 6 is used,
all data in the TX312 is erased. Random transmission may require up to five
minutes (GPS timeout) for setup and transmission. If command 6 is executed
before transmission, random transmission will be canceled.

During GPS acquisition, the LED will light solid green. During transmission,
the LED will light solid red. Command 3 will return 1 value, the command
result code. Zero indicates a successful execution of command 3, but does not
indicate the random transmission has happened or was successful.

5.2.5.5 P127, Command 4: Read TX312 Error Registers

Read error registers of TX312. Requires 10 input locations.

TABLE 5.2-6. P127 Command 4: Read TX312 Error Registers

In Loc Contents

1 Result

Code

2

Number of Errors

3

Command that Caused the Error

4 Error

Code

5

Command that Caused the Error

6 Error

Code

7

Command that Caused the Error

8 Error

Code

9

Command that Caused the Error

10 Error

Code