Appendix D. RAWS-7 Data Format

D-7

16: End (P95)

; Correct Fuel Moisture
17: Polynomial (P55)
1: 1

Reps

2: 28

X Loc [ FuelM ]

3: 28

F(X) Loc [ FuelM ]

4: -220.14 C0
5: 365.89 C1
6: -114.96 C2
7: 0.0

C3

8: 0.0

C4

9: 0.0

C5


; Convert Air Temp to degrees F
18: Z=X*F (P37)
1: 3

X Loc [ AirTemp ]

2: 1.8

F

3: 3

Z Loc [ AirTemp ]


19: Z=X+F (P34)
1: 3

X Loc [ AirTemp ]

2: 32.0

F

3: 3

Z Loc [ AirTemp ]


; Eliminate RH values greater than 100
20: If (X<=>F) (P89)
1: 4

X Loc [ RH ]

2: 3

>=

3: 100

F

4: 30

Then

Do


21: Z=F (P30)
1: 100

F

2: 0

Exponent

of

10

3: 4

Z Loc [ RH ]


22: End (P95)

; correct zero wind speed offset.
23: If (X<=>F) (P89)
1: 5

X Loc [ Wspd ]

2: 4

<

3: 0.4001 F
4: 30

Then

Do


24: Z=F (P30)
1: 0

F

2: 0

Exponent

of

10

3: 5

Z Loc [ Wspd ]


25: End (P95)

Advertising