Windsonic4, 11. wiring for cr200(x) program example – Campbell Scientific WINDSONIC 2-D Sonic Wind Sensors User Manual

Page 28

Advertising
background image

WindSonic Two-Dimensional Sonic Anemometer

*Table 3 Subroutines

End Program

-Input Locations-
1 wnd_dir
2 wnd_spd
3 ws_diag
4 samples

7.4.2 Example CR200(X) Datalogger Program for Measuring a

WindSonic4

TABLE 7-11. Wiring for CR200(X) Program Example

Description Color

CR200(X)

SDI-12 data

Green

C1/SDI-12

SDI-12 power

Red

+12 Vdc

SDI-12 reference

Black

G

Shield Clear

G

'CR200(X) Series Datalogger

Public windsonic(3)

Alias windsonic(1) = wind_direction
Alias windsonic(2) = wind_speed
Alias windsonic(3) = diag

Units wind_direction = degrees
Units wind_speed = m/s
Units diag = unitless


Dim disable_flag
Dim one

Units one = samples

DataTable (stats,TRUE,-1)

DataInterval (0,30,Min)

WindVector (wind_speed,wind_direction,disable_flag,0,0)
FieldNames ("mean_wnd_spd,mean_wnd_dir,std_wnd_dir")
Totalize (1,one,disable_flag)

FieldNames ("n_TOT")
Totalize (1,one,diag<>1)
FieldNames ("diag_1_TOT")

Totalize (1,one,diag<>2)
FieldNames ("diag_2_TOT")
Totalize (1,one,diag<>4)

FieldNames ("diag_4_TOT")
Totalize (1,one,diag<>8)

FieldNames ("diag_8_TOT")
Totalize (1,one,diag<>9)
FieldNames ("diag_9_TOT")

Totalize (1,one,diag<>10)
FieldNames ("diag_10_TOT")