TROUBLE SHOOTING

Front dark - no instrument power.

Process display shows CCCC - Open thermcouple. Short

terminals 1 and 2. Process display should indicate

temperature at back of case. Repair or replace thermocouple.

About Half or Twice Expected Reading - Check position of

°C/°F switch. Short 1 and 2 to read room temperature. 22-30

is °C, 70-85 is °F.

About 30% Error - Wrong thermocouple type.

Disconnect couple.

above 2500°F.

"J" units over range above 14OO°F, "K"

No Heat - No heater power, heater wiring, wrong output module.

Heat Stays On - Welded relay contacts, shorted output module,

or shorted power handler.

Process Display Shows OOOO Or Initially Displays Room

Temperature Then Counts Down Scale As Process Warns - Check

for reversed thermocouple.

Display blinks, entered values change - Caused by electromagnetic

interference

Supress arcing contacts in system to

eliminate high voltage spikes, seperate sensor and controller

power wiring from "dirty" power lines. Ground heated devices.

Unit Repairs

It is recommended that units requiring service be returned

to an authorized service center. When a controller is

returned for service, a note stating the problem should

accompany the unit.

NOTE: Warranty is void when units are modified by the

customer or other non-authorized parties.

A spare parts list can be supplied upon request if complete

model number, serial number and temperature range is supplied.