INTERNAL SWITCHES

Damping Control -To allow the controller to provide automatic

tuning for processes with varying heating characteristics and

with varying heating capabilities, the 6050 offers three

damping choices:

High damping: for over-powered heating systems,

systems with multiple heat lags, and/or poor

coupling between the heater and the temperature

sensor.

Normal: for most standard processes where the

heater is properly sized for the system and

there is good coupling between the heater and

the temperature sensor.

Low damping: for adequately powered systems

with excellent coupling between the heater and

the temperature sensor where quick response and

the tightest possible temperature control are

desired.

Keypad Security -Switch 2 in the open position locks the

operator out of access to all parameters except set point.

CELSIUS/FAHRENHEIT DISPLAY SECTION

Switch 1 allows both displays to read in degrees Celsius or

Fahrenheit, and is indicated on front panel LED's.

WIRING THERMOCOUPLE CIRCUITS

Before wiring, check thermocouple and extension wire to make

sure that they conform to the appropriate thermocouple type

specified on the serial number tag. In thermocouple

circuits, the negative lead is colored red. Extension wires

must be the same alloy and polarity as the couple. The

thermocouple circuit resistance should not exceed 100 OHMS.

Do not run thermocouple leads in the same conduit as the

power lines. If shielded thermocouple is used, terminate the

shield only at the controller end using the corner screw

provided for that purpose.

STANDARD THERMOCOUPLES

I.S.A. TYPE

MATERIALS

COLOR CODE

J

Iron Constantan (I/C)

White(+) Red(-)

K

Chrome1 Alumel (C/A)

Yellow(+)