Installation – Blodgett 40GS-KLS Series User Manual

Page 10

Advertising
background image

8

OM-40GS-KLS

10. The internal gas lines of the unit were cleaned and closed off with a gas cock

before the unit was shipped from the factory. Free all external gas lines of

lint, dirt, metal chips, sealant, grease, oil, and other contaminants, before you

connect the lines to the kettle.

11. Connect the gas cock of the kettle to the gas service main with 3/4 inch IPS line

or approved equivalent

12. Installation must conform with local codes, or in the absence of local codes,

with the National Fuel Gas Code, ANSI Z 223.1-1988 (or latest edition). The

unit should be installed in an adequately ventilated room with a provision for

adequate air supply. The best ventilation will utilize a vent hood and exhaust fan

with no direct connection between the vent duct and the flue. Do NOT obstruct

the flue or vent duct after installation.

In Canada, the installation must conform to the CAN/CGA B149 Installation Codes

for Gas Burning Appliances and Equipment and/or local codes.

13. Adequate space for proper service and operation is required. Do NOT block any

air intake spacings to the combustion chamber or obstruct the air flow by piling

or stacking anything near the kettle.

14. After the kettle has been connected to the gas supply, all gas line joints must be

checked for leaks. DO NOT USE A FLAME TO CHECK FOR LEAKS. A thick soap

solution or other suitable leak detector should be employed.

15. PRESSURE TEST WARNING

a. Test pressure exceeding 1/2 PSIG (3.45 kPa). During pressure testing of the

gas supply piping system at pressures exceeding 1/2 PSIG, the appliance

and its individual shutoff valve must be disconnected from the gas supply

piping system.

b. Test pressure equal to or less than 1/2 PSIG (3.45kPa.) During pressure

testing of the gas supply piping system at pressures equal to or less than

1/2 PSIG, the kettle must be isolated from the gas supply piping system

closing its individual manual shutoff valve

16. Check the following points to confirm that your AHS kettle has been installed

properly.

a. Unit installed on non combustible floor.

b. Enough room between the kettle and nearby objects for cleaning and

service.

c. Minimum clearance of 2 inches from sides and 4” rear clearance.

d. Unit installed under a ventilation hood.

e. Kettle level.

f. Correct amount of water in the jacket.

g. Safety valve outlet pointed down.

h. Connected with a waterproof, 115 volt, 15 amp supply of electric power in

accordance with electrical codes.

i.

Gas lines cleaned before connection.

j.

Gas connected with 3/4 inch pipe or equivalent.

k. Gas line joints checked for leaks.

l.

No obstruction to air supply or venting.

Installation

Advertising