Installation – Blodgett 40GS-KLS Series User Manual

Page 9

Advertising
background image

OM-40GS-KLS 7

The unit should be installed in a ventilated room for efficient performance. items

which may obstruct or restrict the flow of air for combustion and ventilation must be

removed. The area directly around the appliance must be cleared of all combustible

materials.

1. Installation requires connection with gas and electrical services. See items 8 to

14 for details.

2. To protect the unit from damage, leave it on the shipping pallet until the time of

installation. When installation is to begin, cut the straps holding the kettle, and

hoist the kettle straight up off the skid.

3. Unit is for use only on non-combustible floors.

4. Install the unit with a minimum clearance to combustible and non-combustible

construction of two inches at the sides and four inches at rear. Also leave enough

room for cleaning, maintenance, and service.

5. The flue stack and flue elbow shipped with the kettle is the correct height and

shape to give maximum performance. Install the flue stack and flue elbow as

shown on the sketch at left.

Unit must be installed under a ventilation hood only. Installation of a ventilating

hood should comply with local codes and/or ANSI/NFPA-96 Latest Edition. Also,

local codes may require that the kettle be electrically interlocked to shut off

the gas supply and prevent the operation of the unit if the exhaust fan is not

operating or if the fire suppression system is activated. Failure to follow these

instructions can cause bodily injury and/or property damage.

6. To level the unit, adjust leg length by turning the bullet feet.

7. Make sure the water level is correct in the jacket, by confirming that the level

is between the marks on the gauge glass. If the water level is low, follow the

instructions under “Jacket Filling” in the “Maintenance” Section of this manual.

8. To protect personnel from steam coming out of the pressure relief valve, the

open end of the elbow at the outlet must be directed down. If it is not, turn the

elbow to the correct position.

9. Provide 115 VAC, 60 HZ, 1 PH, 15 AMP electrical service for standard unit. Unit

may be equipped for alternate electrical service of 208 VAC or 240 VAC, as

ordered. Use 1/2 inch waterproof conduit and waterproof connections. Observe

local codes and/or The National Electrical Code in accordance with ANSI/NFPA 70

- latest edition. AN ELECTRICAL GROUND IS REQUIRED. The electrical schematic

is located on the inside of the service panel.

In Canada, provide electrical service in accordance with the Canadian Electrical

Code, CSA C22.2 Part 1 and/or local codes.

Installation

WARNING

THIS UNIT MUST BE INSTALLED BY

PERSONNEL WHO ARE QUALIFIED TO

WORK WITH ELECTRICITY AND PLUMBING.

IMPROPER INSTALLATION CAN CAUSE

INJURY TO PERSONNEL AND/OR DAMAGE

TO THE EQUIPMENT. THE UNIT MUST

BE INSTALLED IN ACCORDANCE WITH

APPLICABLE CODES.

NOTICE

TO AVOID DAMAGING PARTS OF THE

BURNER SYSTEM UNDERNEATH THE KETTLE,

LIFT THE UNIT ONLY BY THE RING BENEATH

THE OUTER PORTION OF THE BODY.

WARNING

DO NOT ATTACH THE UNIT TO A TYPE “B”

VENT. FAILURE COULD RESULT IN FIRE OR

PROPERTY DAMAGE.

CAUTION

DO NOT USE KETTLE WITHOUT SUPPLIED

FLUESTACK & ELBOW INSTALLED.

FLUE RISER, 17 INCHES HIGH MUST BE

ATTACHED HERE. NOT SUITABLE FOR

CONNECTION TO TYPE B GAS VENT.

CAUTION

DO NOT CONNECT ANY PIPING TO THIS

PRESSURE RELIEF VALVE. IT MUST BE FREE

TO VENT STEAM AS NEEDED. ELBOW SHOULD

POINT DOWN TOWARD FLOOR. IMPROPER

INSTALLATION WILL VOID WARRANTY!

DANGER

ELECTRICALLY GROUND THE UNIT

AT THE TERMINAL PROVIDED. FAILURE TO

GROUND UNIT COULD RESULT IN

ELECTROCUTION AND DEATH.

Advertising