1 interconnecting – Aico Ei261DENRC User Manual

Page 19

Advertising
background image

4.1 INTERCONNECTING

With interconnected alarms, when one unit detects CO all units alarm. All horns will sound but only units
detecting CO will flash their red lights.

A maximum of twelve Ei261ENRC/261DENRC CO Alarms may be interconnected along with an
Ei128RBU & Ei128COV relay module (see “ACCESSORIES” on page 32).

Alternatively, up to twelve Ei261ENRC /Ei261DENRC CO Alarms and Ei161RC/Ei164RC/Ei166RC
Smoke/Heat Alarms may be interconnected provided an Ei1529RC Remote Control is used in the
system (see “ACCESSORIES” on page 32).

Do not connect these Alarms to any other model produced by another manufacturer, or to any
other model of Ei Alarm, apart from those listed above.
Doing this may damage the Alarms and could
result in a shock or fire hazard.
The interconnect wire (minimum 0.75mm

2

cable) must be treated as if it was Live. It should be insulated

and sheathed.

19

L N IC

L N IC

IC - INTERCONNECT

MAINS
POWER

TO OTHER ALARMS
AS REQUIRED
(see list above)

N - NEUTRAL

L - LIVE

Figure 7 - Interconnect Wiring Diagram

B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 19

Advertising
This manual is related to the following products: