Troubleshooting – Aico Ei261DENRC User Manual

Page 30

Advertising
background image

CO Alarm Memory:

: A unit will indicate if it has been in alarm previously by flashing the red light

for 2 seconds every 40 seconds (2 flashes for 50 ppm CO, 4 flashes for 100
ppm CO and 8 flashes, for 300 ppm CO). When the Test/Hush button is
pressed, the red light flashes (as per Table B on page 8) to indicate the
previous CO alarm level detected. The memory is cleared by holding down
the Test/Hush button until the red light stops flashing.

Digital Display

: Range 50 - 300ppm CO

(Ei261DENRC only)

Resolution 5 ppm CO
With low rechargeable cells - CP
With sensor faulty - SF
With Test/Hush button pressed - previous peak CO level

Dimensions

: 126 x 150 x 42 mm.

Weight

: 330g.

13. TROUBLESHOOTING

1. ALARM DOES NOT WORK WHEN THE TEST BUTTON IS PRESSED:

- Check that the green mains power light is on. If it is off check the wiring, fuse, circuit breakers etc.

- Hold the Test/Hush button down for at least 5 seconds.

2. ALARM BEEPS AND AMBER LIGHT FLASHES EVERY 40 SECONDS:

- If the alarm beeps and the amber fault light flashes every 40 seconds, the CO sensor is probably

defective.

30

B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 30