Installation

512685

14

Figure 6

Figure 7

H318I

1

NOTE: Where the exhaust duct pierces a
combustible wall or ceiling, the opening must be

3

Clearance per Local Codes

4

No Screen or Cap

sized per local codes.

5

Clean Out Cover

Inspect Monthly

2

Wall

H318I

2

3

4

EXHAUST

OUTLET

K

J

I

H

G

F

E

D

C

B

A

5

30°

1

EXHAUST AIR FLOW

MAXIMUM LENGTH OF DUCT

30 feet (9.1 m)

HORIZONTAL EXHAUST INSTALLATION

AIR

FLOW

D319I

1

Roof

2

Wall

3

2 in. (5 cm) Minimum

4

NOTE: Where the exhaust duct pierces a
combustible wall or ceiling, an opening must
be sized as shown or per local codes.

1

3

4

CONNECT TO DRYER

VERTICAL EXHAUST INSTALLATION

2

To reduce the risk of fire and the
accumulation of combustion gases, DO NOT
exhaust dryer air into a window well, gas
vent, chimney or enclosed, unventilated
area, such as an attic, wall, ceiling, crawl
space under a building or concealed space
of a building.

W045

WARNING