Section 2 Installation

2.4.5 PM2 Sensors in

Non-Full Pipes

The ChannelMag PM Series sensors are used in partially filled pipes from 20” - 120” (500 - 3000

mm) diameter. For pipes 20” - 36” (500 - 915 mm) a single ChannelMag sensor is installed in a

retention band at the bottom of a horizontal pipe. For larger pipes two sensors are used at the

bottom of the pipe, with their center lines equally dispersed at 15 degrees from the pipe center.

For partially filled pipes a hydrostatic level transducer is incorporated in a ramp on the upstream

end of the sensor. The level transducer cable includes a “breather” tube, which is vented in the

remote 4411e transmitter, or in a junction box when the cable is longer than 33 feet (10 m). The

cables are run in plastic conduits to the pipe exterior.

Partially Filled Pipes -- Single Sensor

20” - 36” (500 - 915 mm) Diameters

Partially Filled Pipes -- Double Sensors

38” - 120” (920 - 3000 mm) Diameters