Additional Installation Tips

6.4 Ambient Temperature

The maximum ambient temperature for the operator panel is provided in the
specifications. The ambient temperature refers to the temperature in the device
cabinet which cools the panel’s electronics.

Operator
panel

Power

Power

Power

30 °C outside

Top
50 °C inside

Bottom
40 °C inside

Middle
45 °C inside

Airflow

Axial fan
120 x 120 mm

5354

In most cases, the ambient temperature for the operator panel is significantly
higher than the device cabinet’s ambient temperature.
If the cabinet is tall and there are a number of heat-generating devices, the
temperature at the top of the cabinet will be considerably higher than the
theoretical temperature increase that would be expected. All electronics are
sensitive to heat. The lifespan of an electrolytic capacitor is cut in half with an 8-10
° increase in temperature. A 15-20 ° temperature increase results in a quarter of the
lifespan etc.
Rittal has a good program for estimating the anticipated average temperature in
the cabinet as well as a large program for controlling the temperature in the device
cabinet.
An enamel-coated steel cabinet has a radiant heat value of 5.5 W/m

2

and degrees

C.
Installing a fan inside the cabinet will even out the temperature, while moving air
provides considerably better cooling than still air. A suitable fan is a 120 x 120 mm
axial fan, available in 24 V DC, 115 and 230 V AC.
Install the fan so that it sits in the cooler area and will blow cold air against the
operator panel. If the fan is mounted at the top and sucks air upwards, the fan’s
ambient temperature will be higher = shorter lifespan.
A good fan with a ball-bearing mounting has an expected lifespan of at least
40,000 hours (not a guaranteed lifespan) at 40 °C. This corresponds to at least 4
years of continuous use. If a thermostat is installed, the fan only needs to come
on when needed.
Large graphic terminals draw only one fifth of the current when the background
lighting is off. The loss effect drops from e.g. 25 W to only 5 W.
The operator panel’s loss effect = supply voltage x current. Virtually no power goes
to external users and no loss effects due to inputs.

Beijer Electronics, MAEN011A