6 galvanic isolation, Galvanic isolation, Additional installation tips – Beijer Electronics iX Panel TA150 EN User Manual

Page 21

Advertising
background image

Additional Installation Tips

6.6 Galvanic Isolation

USB

USB

RS232

RS422/485

+24 V DC

0 V

Filter

DC/DC
galvanic isolation

VCC

0 V (GND)

DC/AC

CFL

Ethernet

Internal electronic

1.5 m

5356

The operator panel has galvanic isolation against the 24 V DC feed but no galvanic
isolation between the communication ports for RS232, RS422/485 and USB.
Only the Ethernet connection has galvanic isolation.

*

*

*

*

*

*

*

*

*

Operator panel

Modular controller

Printer

PC

PC

Not same ground potential

* = Internal 0 V (GND) connection

Power CPU

COM COM2

RS422

RS232

USB

5357

When a PC is connected to the panel, the panel’s internal 0 V (GND) will be
connected to the protective ground via the PC.
A number of USB devices can have the shield connected together with the
protective ground. Here, the panel’s 0 V (GND) is connected to the protective
ground when, for example, a USB memory stick, keyboard or similar device is
plugged in.
If a number of units are connected that have a 0 V and a ground connection, and
these are connected to various grounding points, there is a substantial risk of
problems. Grounding currents go through communication cables, the rear plate
of the controller, and internally in the operator panel, and can cause errors.
Use external units to improve communication and achieve galvanic isolation.
Westermo has good industry-standard insulators that are also insulated from the
24 V DC feed.

Note:
It is very important to make sure that the 24 V feed in the external insulation unit is not
connected to one of the communication outlets. If it does not have 100% insulation
against the 24 V feed, disturbances and grounding currents from the 0 V on the 24 V
side will disrupt communication.
Using this type of unit solves one problem but creates a larger problem! A substandard
installation may work now, but problems may arise when other devices are connected.