Group 5 : Fieldbus communications (Level 2) 

Parameter 

Number 

Register 
Number 

Description 

Range

Scaling 

Type

P5‐01 

501 

Fieldbus drive address 

0…63

1 = 1 

P5‐02 

502 

CANbus baudrate 

125kbps
250kbps 
500kbps 
1Mbps 

0 = 125kbps 
1 = 250kbps 

P5‐03 

503 

Modbus baudrate 

9.6kbps,
19.2kpbs, 
38.4kpbs, 
57.6kpbs, 
115 kbps  

0 = 9.6kbps 
1 = 19.2kpbs 

P5‐04 

504 

Modbus data format 

N‐1 : None Parity 1 stop bit
N‐2 : None parity 2 stop bits 
O‐1 : Odd parity 1 stop bit 
E‐1 : Even parity 1 stop bit 

0 = N‐1 
1 = N‐2 

P5‐05 

505 

Comms loss timeout 

0...0.1... 5.0

1 = 0.1s 

P5‐06 

506 

Communications loss action 

0: Trip
1: Ramp to Stop then trip 
2: Ramp to stop (No trip) 
3: Preset speed 8 

1 = 1 

P5‐07 

507 

Fieldbus ramp control 

0: Disable
1: Enable 

1 = 1 

P5‐08 

508 

Anybus module output process data 4 

0: Torque (%)
1: Power (x.xx kW) 
2: Digital input status 
3: 2

nd

 analog input (%) 

4. Power stage temperature 

1=1 

 
 

 